Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the acf domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /www/wwwroot/yuzantech.com/wp-includes/functions.php on line 6131

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the unlimited-elements-for-elementor domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /www/wwwroot/yuzantech.com/wp-includes/functions.php on line 6131

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the dynamic-content-for-elementor domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /www/wwwroot/yuzantech.com/wp-includes/functions.php on line 6131
YZIBxLE Series Intelligent Residual Current Operated Monitoring Circuit Breakers – Zhejiang Yuzan Tech
gsfm (1)
Yuzan Tech Strengthens Global Presence with Intelligent Power Environment Solutions
Data-Center-Management-System-1
Passive Bluetooth Lock Intelligent Management System Makes a Grand Debut, Ushering in a New Era of Battery-Free Operation and Maintenance Safety Management
YZIBx-Series-Intelligent-Circuit-Breaker-Products-1-1024x769
Intelligent Circuit Breaker Series: The Smart Core of Modern Power Distribution

ABOUT US

About Us - Introducing our team,
mission, and values.

YZIBxLE Series Intelligent Residual Current Operated Monitoring Circuit Breakers

Model

YZIB3LE-63M
YZIB5LE-63M3
YZIB5LEU-63M3
YZIB3LE-100M
YZIB5LE-100M3
YZIB5LEU-100M3

Parameters

MODEL YZIB3LE-63M

YZIB5LE-63M3

YZIB5LEU-63M3 YZIB3LE-100M YZIB5LE-100M3 YZIB5LEU-100M3
Parameters Pole Number 1P, 1P+N, 3P, 3P+N
Rated Voltage Ue(V) AC230 (1P, 1P+N) (customizable)

AC400 (3P, 3P+N) (customizable)

Rated Current (A) 6, 10, 16, 20, 25, 32, 40,50, 63 70, 80 70, 80, 100
Rated Insulation Voltage Ui(V) 500
Rated Impulse Withstand Voltage Uimp (kV) 4
Rated Ultimate Short-Circuit Breaking Capacity 10 6
Rated Service Short-Circuit Breaking Capacity 7.5 6
Rated Operating Frequency f(Hz) 50/60
Rated Residual Making and Breaking Capacity Im (A) 1000
Release Type Type B, Type C, Type D
Residual Current Tripping Characteristic Type AC
Mechanical Life (Times) 20000
Electrical Life (Times) 10000
Protection Functions Overload Delay Protection No action within 1h (2h) when energized at 1.13In; action within 1h (2h) when energized at 1.45In; 2h for products ≥80AAction within (1~60)s when energized at
 55In and In≤32A; action within (1~120)s when In>32A
Short-Circuit Instantaneous Protection No action within 100ms when energized at Type B (3In), Type C (5In), Type D (10In)

 

Action within 100ms when energized at Type B (5In), Type C (10In), Type D (15In)
Electronic Overload Protection Adjustable from 1A~1.2In, default action at 1.2In
Electronic Overload Protection Operation Time Adjustable from 1~3600s, default action at 15s
Over-Voltage Protection Adjustable from 240~300V, default action at 275V
Over-Voltage Protection Operation Time Adjustable from 1~15s, default action at 9s
Under-Voltage Protection Adjustable from 150~200V, default action at 160V
Under-Voltage Protection Operation Time Adjustable from 1~15s, default action at 3s
Over-Temperature Protection Adjustable from 1~120℃, default action at 90℃
Over-Temperature Protection Operation Time Adjustable from 1~15s, default action at 5s
Power Limitation Adjustable from 220~1.5Pn, default action at 1.5Pn
Power Limitation Operation Time Adjustable from 1~10s, default action at 5s
Phase Failure Protection For 3P+N products, the circuit breaker acts (≤1s) when any phase is missing
Residual Current Protection Adjustable from 5~300mA, default action at 100mA
Residual Current Protection Operation Time Implemented in accordance with Table 2 of GB/T 16917.1-2014
Arc Fault Protection (Optional □) The circuit breaker trips for protection when an arc short-circuit fault occurs
Three-Phase Unbalance Protection (Optional □) For 3P+N products, the circuit breaker trips for protection when current is unbalanced
Early Warning Overcurrent Early Warning (A) Adjustable from 1A~1In, default at 0.8In
Overvoltage Early Warning (V) Adjustable from 240~280V, default at 250V
Undervoltage Early Warning (V) Adjustable from 150~200V, default at 190V
Residual Current Early Warning (mA) Adjustable from 5~300mA, default at 50mA
Over-Temperature Early Warning (℃) Adjustable from 1~120℃, default at 65℃
Overload Early Warning (W) Adjustable from 220~1.5Pn, default at 0.8Pn
Alarm Overcurrent Alarm (A) Adjustable from 1A~1In, default at 1In; not available for monitoring version
Overvoltage Alarm (V) Adjustable from 240~300V, default at 260V; not available for monitoring version
Undervoltage Alarm (V) Adjustable from 150~200V, default at 180V; not available for monitoring version
Residual Current Alarm (mA) Adjustable from 5~300mA, default at 100mA; not available for monitoring version
Over-Temperature Alarm (℃) Adjustable from 1~120℃, default at 75℃; not available for monitoring version
Overload Alarm (W) Adjustable from 220~1.5Pn, default at 1.0Pn; not available for monitoring version
Remote Control Remote Tripping Remote control of circuit breaker tripping via Web terminal or APP
Remote Closing Remote control of circuit breaker closing via Web terminal or APP
Measurement Voltage 0.7Un≤U≤1.3Un, accuracy ±0.5%
Current Accuracy ±1.5% when I≤0.05In; accuracy ±0.75% when 0.05In<I≤0.2In; accuracy ±0.5% when 0.2In<I≤1.2In
Power Accuracy ±2% when 0.05In≤I≤0.1In; accuracy ±1% when 0.1In<I≤1.2In
Electrical Energy Accuracy ±2% when 0.05In≤I≤0.1In; accuracy ±1% when 0.1In<I≤1.2In
Communication Communication Interface RS485 (Standard Configuration)
Communication Protocol Modbus-RTU
Communication Baud Rate Default 9600bps, optional 2400bps, 4800bps, 9600bps / Default 9600bps, optional 1200bps, 4800bps, 9600bps
Additional Functions Wave Recording Function (Optional □) Real-time collection of circuit breaker voltage and current waveforms for load identification (for 1P+N, 1P products)
Arc Fault Protection (Optional □) Detect faulty arcs in the circuit and alarm if faulty arcs occur (for 1P+N products)
Product Installation Dimensions

Dimension Drawing of YZIB3LE-63 (100) M/ M3

Dimension Drawing of YZIB5LE-63 (100) M/ M3

Dimension Drawing of YZIB5LEU-63 (100) M/ M3